Sharys Micro DC systems from 7.5 to 100A |
|
|
|
|
|
|
SHARYS MICRO is a direct-current (48 V DC) power system designed for installation in 19" cabinets.
It can house the SHARYS PLUS controller and at most two SHARYS rectifier modules working in parallel. Internally the system integrates all the input and output sectioning and protecting members.
ADVANTAGES
- 19" 6U subrack
- protected battery output
- four protected load outputs
- rear connection
- remote access via SNMP, Internet, Java
(with optional NET VISION )
- dry contacts (via optional dry contacts interface)
TECHNICAL DATA
| With rectifier model |
SHARYS
400 |
SHARYS
800 |
SHARYS
1600 |
SHARYS
2700 |
| Input voltage |
230V AC +20% -40%* |
| Input frequency |
from 47.5 to 63 Hz |
| Input power factor |
³ 0.99 (nominal conditions) |
| AC distribution toward rectifier |
fuse (size 10 x 38) 1 pole |
| Output voltage |
48V DC (42-58 V DC) |
| Output current at 53.3V** |
15A |
30A |
60A |
100A |
| Max. output power** |
800W |
1600W |
3200W |
5400W |
| Efficiency (typical) |
³ 0.90 |
³ 0.90 |
³ 0.91 |
³ 0.92 |
| Options |
Battery Low Voltage Disconnector,
DC distribution (fuse or MCCB),
dry contacts, thermal probe,
voltage temperature compensation,
second battery fuse,
remote supervision through NET VISION |
| Color |
RAL7012 |
| Dimensions (W x D x H) mm |
19" x 500 x 262 (6U) |
| Weight |
20 kg (without modules) |
| Protection degree |
IP20 (with modules inserted) |
| Working temperature |
|
|
without derating
with derating |
-5 °C to +45 °C
+45 °C to +55 °C |
* from -20% to -40% linear derating from 100% to 60% Pmax
** with two rectifiers modules |
|