Sharys Mini DC systems from 7.5 to 200A |
|
|
|
|
|
|
SHARYS MINI is a direct-current (48V DC) power system designed for installation in 19" cabinets.
It can house the SHARYS PLUS controller and 4 or 5 (depending on the model) SHARYS rectifier modules working in parallel. Internally the system integrates all the input and output sectioning and protecting members.
ADVANTAGES
- 19" 12U subrack
- protected battery output
- fitting for DC distribution
- rear connection
- remote access via SNMP, Internet, Java
(with optional NET VISION )
- dry contacts (via optional dry contacts interface)
TECHNICAL DATA
| With rectifier model |
SHARYS
400 |
SHARYS
800 |
SHARYS
1600 |
SHARYS
2700 |
| Input voltage |
400V AC three-phase + N
or 230V AC single-phase +20% -40%* |
| Input frequency |
from 47.5 to 63 Hz |
| Input power factor |
³ 0.99 (nominal conditions) |
| AC distribution toward rectifier |
fuse (size 10 x 38) 1 pole |
| Output voltage |
48V DC (42-58V DC) |
| Output current at 53.3V** |
37.5A |
75A |
120A |
200A |
| Max. output power** |
2000W |
4000W |
6400W |
10800W |
| Efficiency (typical) |
³ 0.90 |
³ 0.90 |
³ 0.91 |
³ 0.92 |
| Options |
Battery Low Voltage Disconnector,
DC distribution (fuse or MCCB),
dry contacts, thermal probe,
voltage temperature compensation,
second battery fuse,
remote supervision through NET VISION |
| Color |
RAL7012 |
| Dimensions (W x D x H) mm |
19" x 500 x 524 (12U) |
| Weight |
25 kg (without modules) |
| Protection degree |
IP20 (with modules inserted) |
| Working temperature |
|
|
without derating
with derating |
-5 °C to +45 °C
+45 °C to +55 °C |
* from -20% to -40% linear derating from 100% to 60% Pmax
** with complete rectifier configuration |
|