Technical Specifications: UPS Multi Dialog 10-30 (MDT - MDM) |
|
|
|
|
|
«back
| MODELS |
MDM 1000 |
MDM 1500 |
MDM 2000 |
MDT 1000 |
MDT 1500 |
MDT 2000 |
MDT 3000 |
| INPUT |
| Voltage tolerance |
± 20% |
| Frequency tolerance |
45/65 Hz |
| Voltage |
230 Vac single-phase or 400 Vac
three-phase + N |
400 Vac three-phase + N |
| Rated power |
10000 VA |
15000 VA |
20000 VA |
10000 VA |
15000 VA |
20000 VA |
30000 VA |
| Power factor |
0.95 |
| Current distorsion |
sine absorbing (MULTI DIALOG CLEAN
option) |
| OUTPUT AND INVERTER OUTPUT |
| Rated power |
10000 VA |
15000 VA |
20000 VA |
10000 VA |
15000 VA |
20000 VA |
30000 VA |
| Dynamic stability |
± 5% in 10 µs |
| Number phases |
1 |
3 |
| Active power |
8000 W |
12000 / 10500 W Three/single phase version
|
16000 / 12000 W Three/single-phase version
|
8000 W |
12000 W |
16000 W |
24000 W |
| Static stability |
± 1% |
| Crest factor (Ipeak/Irms) |
3 : 1 |
| Output current |
44A |
65A |
87A |
15 A |
22 A |
29 A |
43.5 A |
| Overload |
125% 150% 200% of the rated current
for 10' / 1' / 7" |
| Voltage distortion with linear load |
2% |
| Waveform |
Sinewave |
| Frequency |
50/60 Hz selectable |
| BY PASS |
| Rated frequency |
50/60 Hz |
| Number phases |
1 |
3 |
| Rated voltage |
230 Vac |
400 Vac |
| Frequency tolerance |
± 2% (selectable from ± 1% to ± 5%)
|
| Voltage tolerance |
± 15% (selectable from ± 5% to ±
25%) |
| BATTERIES |
| Type |
Maintenance-free sealed lead acid
|
| Recharge time |
6 h |
8 h |
| ENVIRONMENTAL |
| Relative humidity |
95% non condensing |
| Operating temperature |
0 ÷ 40 °C |
| Noise |
<56 dBA at 1 m |
| AC/AC efficiency |
>92% |
| EMC conformance |
EN 50091-2 Lev.A and Directive
73/23 EEC, 93/68 EEC, 89/336 EEC |
| Color |
Light grey RAL 7035 |
| Remote controls |
EPO and bypass |
| Remote signals |
voltage free contacts |
| Safety compliance |
EN 62040-1 |
| Protection rating |
3 |
| Communication |
Double RS232/C |
| OPTIONS |
| Double serial port board Multicom 352 |
yes |
| Communication software “full” version |
yes |
| JBUS/Modbus communication board Multicom 302 |
yes |
| LCD-based remote control panel |
yes |
| LED-based remote control panel |
yes |
| Extended runtime battery boxes |
yes |
| Parallel kit (to order with the UPS) |
yes |
| CLEAN version |
yes |
| Network adapter for slot NetMan 102 |
yes |
| Isolation transformer module |
yes |
| |
| OPTIONS |
| CLEAN version |
x |
x |
x |
x |
x |
x |
x |
| Multicom 352 |
x |
x |
x |
x |
x |
x |
x |
| Multicom 302 |
x |
x |
x |
x |
x |
x |
x |
| Netman 102 |
x |
x |
x |
x |
x |
x |
x |
|
|
«back |