The RE Series has a transformer with multiple sockets, each of which is connected electrically to a solid state switch. These switches are governed by a control plate with a built-in microprocessor, which controls the output voltage and, depending on its level, selects one socket or the other in order to obtain the optimal voltage level with the pre-programmed accuracy. It has a servo-system that compares the output voltage instead of controlling the input voltage.
With similar technology, the PLC series also has a transformer with galvanic isolation of low primary-secondary capacity, thus achieving a perfectly stable voltage and the elimination of all kinds of electrical noise.
Both series offer the assurance of a perfectly stabilised, “filtered” line supply.
Main features
- Powers from 300 VA to 200 kVA
- Single phase and three phase (independent control)
- 0 harmonic distortion and efficiency >95%
- Output accuracy of 2%
- The fastest regulation on the market: 20 ms
- Input margin of ±15% (standard). ±20% or ±25% on request
- Automatic static By-pass per phase (0 ms transfer)
- Controlled by microprocessor with interface via free power contacts
Commercial characteristics
- Flexibility: devices tailor made for customers (VIN / VOUT)
- Technology based on transformers of proven reliability
- 100% independent phase regulation, standard
- Protection of static by-pass by phase, standard
- No mechanical components: no maintenance cost
- Built-in voltmeter, free from 20 kVA
- CE and TUV GS markings. Manufactured under ISO9001
- World Leaders in Line Conditioners since 1970
Applications
- Peripherals: printers, modems, …
- Satellite stations
- Scientific and electronic equipment
- Critical medical processes
- Chemical laboratory equipment
- Sensitive electronic components
| Input |
|
 |
 |
 |
Single phase Voltage |
120 V, 220 V, 230 V, 240 V |
| Three phase voltage |
208 V, 220 V, 230 V, 240 V, 380 V, 400 V, 415 V |
| Input range |
±15% |
| Frequency |
48 ¸ 63 Hz |
| Power factor |
0,95 |
  |
 |
Single phase Voltage |
120V, 220V, 230V ó 240V |
| Three phase voltage |
208 V, 220 V, 230 V, 240 V, 380 V, 400 V, 415 V + N + T |
| Accuracy |
>±2% |
| Nominal power |
According to the table |
| Frequency |
48 ¸ 63 Hz |
| Current |
According to the table |
| Harmonic distortion |
Nil |
| Response time |
20 ms |
| Efficiency |
According to the power, 0,90 ¸ 0,98 |
| Permissible overload |
100% for 1 minute
200% for 20 seconds
1.000% for 50 ms. |
  |
 |
Operating temperature |
—40ºC ¸ +45ºC |
| Relative humidity |
0% a 95%, non-condensing |
| Maximum altitude |
3.000 m. |
| MTBF |
60.000 hours |
| MTTR |
30 min |
| Noise level at 1m |
<35 dB |
| Natural cooling |
Below <36 kVA |
| Permissible power factor of the load |
PLC with transformer (T): >40 dB |
| Noise level attenuation in common mode |
PLC with transformer (NS): >120 dB |
  |
 |
MODEL RE2 / PLC2
Single phase
230 V ±15% / 230 V |
Pot.
(kVA) |
Int.
(A) |
MODEL RE2/PLC2
Three phase
3 x 400 V ±15% / 3 x 400 V |
Pot.
(kVA) |
Int.
(A) |
|
 |
RE 309-2 / 2T |
0,3 |
1,3 |
RET 3-4 /4T |
3 |
4,3
|
  |
 |
RE 609-2 / 2T |
0,6 |
2,6 |
RET 6-4 /4T |
6 |
8,7
|
  |
 |
RE 1.009-2 / 2T |
1 |
4,3 |
RET 9-4 /4T |
9 |
13
|
  |
 |
RE 2.009-2 / 2T |
2 |
8,7 |
RET 13-4 /4T |
13,5 |
20
|
  |
 |
RE 3.009-2 / 2T |
3 |
13 |
RET 18-4 /4T |
18 |
26
|
  |
 |
RE 4.509-2 / 2T |
4,5 |
20 |
RET 27-4 /4T |
27 |
39
|
  |
 |
RE 6.009-2 / 2T |
6 |
26 |
RET 36-4 /4T |
36 |
52
|
  |
 |
RE 9.009-2 / 2T |
9 |
39 |
RET 50-4 /4T |
50 |
72
|
  |
 |
RE 12.009-2 / 2T |
12 |
52 |
RET 60-4 /4T |
60 |
87
|
  |
 |
RE 15.009-2 / 2T |
15 |
65 |
RET 75-4 /4T |
75 |
108
|
  |
 |
RE 20.009-2 / 2T |
20 |
87 |
RET 100-4 /4T |
100 |
145
|
  |
 |
RE 25.009-2 / 2T |
25 |
109 |
RET 125-4 /4T |
125 |
181
|
  |
 |
RE 30.009-2 / 2T |
30 |
130 |
RET 150-4 /4T |
150 |
217
|
  |
For any other power, voltages and/or specifications and dimensions, please consult.
|